| Overview | |
| Presentation | Highly compact, energy efficient 3-phase UPS for data center, facility and industrial applications. to be used with external battery cabinets. Please click here for additional runtime information. |
| Lead time | Usually Ships within 2 Weeks |
| General | |
| Provided equipment | Built-in modbus protocol adapter
Dust filter Installation guide Integrated network management Seismic compliance Top and bottom cable entry |
| Bypass voltage tolerance | +/- 10 % settable from +/- 4/6/8 and 10 % |
| Max bypass input current | 289 A |
| Bypass current protection | 400 A |
| Physical | |
| Colour | White |
| Depth | 85.4 cm |
| Height | 197 cm |
| Net weight | 724 kg |
| Width | 105.2 cm |
| Input | |
| Network frequency | 40…70 Hz |
| Max short time withstand current | 65 kA |
| Input voltage limits | 250…600 V adjustable
320…456 V 380 V 320…480 V 400 V 320…498 V 415 V |
| Input voltage | 400 V 3 phases |
| Inputvolt_other | 380 V
415 V |
| Maximum input current | 328 A |
| Switching current capacity | 400 A |
| Input harmonic distortion | Less than 3 % for full load |
| Input protection type | GL fuse |
| Output | |
| Rated power in W | 180000 W |
| Maximum configurable power in W | 180000 W |
| Harmonic distortion | Less than 2 % |
| Output frequency | 50/60 Hz +/- 1 Hz sync to mains
50/60 Hz +/- 1 Hz unsynchronised |
| Outputvolt_other | 380 V
415 V |
| Crest factor | Unlimited |
| UPS type | Double conversion online |
| Wave type | Sine wave |
| Output connector type | Hard wire 4-wire (3P + E) 1
Hard wire 5-wire (3P + N + E) 1 |
| Neutral output current | 289 A |
| Bypass type | Built-in static bypass |
| Output voltage | 400 V 3 phases |
| Output voltage tolerance | +/- 1% static and +/- 3% at 100% load step |
| Output harmonic distortion | < 2% linear load and < 3% non-linear load |
| Output overload operation | 10 minutes at 125% and 60 seconds at 150% |
| Conformance | |
| Product certifications | C-Tick
CE ETL RCM |
| Standards | EN/IEC 62040-1
EN/IEC 62040-2 EN/IEC 62040-3 IBC 2012 and CBC2013 to Sds=2.02g ISTA 2B OSHPD UL 1778 |
| Environmental | |
| Ambient air temperature for operation | 0…40 °C |
| Relative humidity | 0…95 % |
| Operating altitude | 0…3333 ft |
| Ambient air temperature for storage | -25…55 °C |
| Storage altitude | 0.00…14999.82 m |
| Acoustic level | 65 dBA |
| Heat dissipation | 24570 Btu/h |
| IP degree of protection | IP20 |
| Batteries & Runtime | |
| Battery type | External battery system |
| Battery voltage | 480 V |
| Discharge battery voltage | 384 V |
| Max current discharge | 393 A |
| Communications & Management | |
| Control panel | 7″ touch screen display |
| Alarm | Audible and visible alarms prioritized by severity |
| Free slots | 2 |
| Emergency power off | Yes |
| Packing Units | |
| Package 1 Weight | 770 kg |
| Package 1 Height | 215.6 cm |
| Package 1 width | 149 cm |
| Package 1 Length | 106 cm |
| Offer Sustainability | |
| EU RoHS Directive | Under investigation |
| Optimized Energy Efficiency | Energy efficient product |
| Contractual warranty | |
| Warranty | 1 year on-site repair or replace with factory authorized Start-Up |
English