| Overview | |
| Lead time | Usually Ships within 2 Weeks | 
| General | |
| Provided equipment | Battery modules ship installed CD with software Network management card Power modules ship installed Smart UPS signalling RS-232 cable Start-up service User manual Bolt down brackets Installation guide | 
| Physical | |
| Depth | 83.8 cm | 
| Height | 149.1 cm | 
| Net weight | 627 kg | 
| Width | 52.3 cm | 
| Input | |
| Network frequency | 40…70 Hz auto-sensing | 
| Number of input connectors | 1 hard wire 5-wire (3P + N + E) | 
| Input voltage limits | 340…460 V adjustable 400 V 304…477 V | 
| Input voltage | 400 V 3 phases | 
| Inputvolt_other | 380 V 415 V | 
| Maximum input current | 14 A | 
| Switching current capacity | 16 A | 
| Input harmonic distortion | Less than 5 % for full load | 
| Input protection type | 3-pole circuit breaker | 
| Output | |
| Rated power in W | 8000 W | 
| Maximum configurable power in W | 8000 W | 
| Harmonic distortion | Less than 5 % | 
| Output frequency | 47…53 Hz for 50 Hz nominal sync to mains 50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised | 
| Outputvolt_other | 380 V 415 V | 
| Crest factor | Unlimited | 
| UPS type | Double conversion online | 
| Wave type | Sine wave | 
| Output connector type | Hard wire 4-wire (3P + E) 1 Hard wire 5-wire (3P + N + E) 1 | 
| Connections – terminals | 1 screw terminals | 
| Bypass type | Built-in maintenance bypass Built-in static bypass | 
| Output voltage | 400 V 3 phases | 
| Output voltage tolerance | +/- 5% static and 100% load step | 
| Output harmonic distortion | < 2% for 0 to 100% linear load and < 5% for full non-linear load | 
| Output overload operation | 10 minutes at 125% and 60 seconds at 150% | 
| Required output current protection | 16 A | 
| Conformance | |
| Product certifications | CE | 
| Standards | EN 50091-2 EN/IEC 62040-3 EN/IEC 62040-1-1 IEC 61000-3-2 IEC 61000-3-3 ISO 14001 ISO 9001 VFI-SS-111 | 
| Environmental | |
| Ambient air temperature for operation | 0…40 °C | 
| Relative humidity | 0…95 % | 
| Operating altitude | 0…3333 ft | 
| Ambient air temperature for storage | -15…45 °C | 
| Storage altitude | 0.00…15240.00 m | 
| Acoustic level | 51.3 dBA | 
| Heat dissipation | 1501 Btu/h | 
| IP degree of protection | IP51 | 
| Batteries & Runtime | |
| Battery type | Lead-acid battery | 
| Number of battery filled slots | 4 | 
| Number of battery free slots | 0 | 
| Battery recharge time | 5 h | 
| Number of battery replacement quantity | 4 | 
| Additional information | Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage | 
| Liquid value | 0 | 
| Battery voltage | +/- 192 V (split battery referenced to neutral) | 
| Discharge battery voltage | +/- 154 V | 
| Max current discharge | 109.7 A | 
| Battery overload operation | 10 minutes at 125% and 60 seconds at 150% | 
| Communications & Management | |
| Control panel | Multifunction LCD status and control console | 
| Alarm | Alarm when on battery : distinctive low battery alarm : configurable delays | 
| Free slots | 0 | 
| Preinstalled device | Network management card 2 with environmental monitoring | 
| Emergency power off | Yes | 
| Packing Units | |
| Package 1 Weight | 657 kg | 
| Package 1 Height | 164.3 cm | 
| Package 1 width | 65 cm | 
| Package 1 Length | 106.2 cm | 
| Offer Sustainability | |
| EU RoHS Directive | Pro-active compliance (Product out of EU RoHS legal scope) EU RoHS Declaration | 
| Contractual warranty | |
| Warranty | 1 year on-site repair or replace | 
 