Overview | |
Lead time | Usually Ships within 2 Weeks |
General | |
Provided equipment | Battery modules ship installed
CD with software Network management card Power modules ship installed Smart UPS signalling RS-232 cable Start-up service User manual Bolt down brackets Installation guide |
Physical | |
Depth | 83.8 cm |
Height | 149.1 cm |
Net weight | 627 kg |
Width | 52.3 cm |
Input | |
Network frequency | 40…70 Hz auto-sensing |
Number of input connectors | 1 hard wire 5-wire (3P + N + E) |
Input voltage limits | 340…460 V adjustable 400 V
304…477 V |
Input voltage | 400 V 3 phases |
Inputvolt_other | 380 V
415 V |
Maximum input current | 14 A |
Switching current capacity | 16 A |
Input harmonic distortion | Less than 5 % for full load |
Input protection type | 3-pole circuit breaker |
Output | |
Rated power in W | 8000 W |
Maximum configurable power in W | 8000 W |
Harmonic distortion | Less than 5 % |
Output frequency | 47…53 Hz for 50 Hz nominal sync to mains
50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised |
Outputvolt_other | 380 V
415 V |
Crest factor | Unlimited |
UPS type | Double conversion online |
Wave type | Sine wave |
Output connector type | Hard wire 4-wire (3P + E) 1
Hard wire 5-wire (3P + N + E) 1 |
Connections – terminals | 1 screw terminals |
Bypass type | Built-in maintenance bypass
Built-in static bypass |
Output voltage | 400 V 3 phases |
Output voltage tolerance | +/- 5% static and 100% load step |
Output harmonic distortion | < 2% for 0 to 100% linear load and < 5% for full non-linear load |
Output overload operation | 10 minutes at 125% and 60 seconds at 150% |
Required output current protection | 16 A |
Conformance | |
Product certifications | CE |
Standards | EN 50091-2
EN/IEC 62040-3 EN/IEC 62040-1-1 IEC 61000-3-2 IEC 61000-3-3 ISO 14001 ISO 9001 VFI-SS-111 |
Environmental | |
Ambient air temperature for operation | 0…40 °C |
Relative humidity | 0…95 % |
Operating altitude | 0…3333 ft |
Ambient air temperature for storage | -15…45 °C |
Storage altitude | 0.00…15240.00 m |
Acoustic level | 51.3 dBA |
Heat dissipation | 1501 Btu/h |
IP degree of protection | IP51 |
Batteries & Runtime | |
Battery type | Lead-acid battery |
Number of battery filled slots | 4 |
Number of battery free slots | 0 |
Battery recharge time | 5 h |
Number of battery replacement quantity | 4 |
Additional information | Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage |
Liquid value | 0 |
Battery voltage | +/- 192 V (split battery referenced to neutral) |
Discharge battery voltage | +/- 154 V |
Max current discharge | 109.7 A |
Battery overload operation | 10 minutes at 125% and 60 seconds at 150% |
Communications & Management | |
Control panel | Multifunction LCD status and control console |
Alarm | Alarm when on battery : distinctive low battery alarm : configurable delays |
Free slots | 0 |
Preinstalled device | Network management card 2 with environmental monitoring |
Emergency power off | Yes |
Packing Units | |
Package 1 Weight | 657 kg |
Package 1 Height | 164.3 cm |
Package 1 width | 65 cm |
Package 1 Length | 106.2 cm |
Offer Sustainability | |
EU RoHS Directive | Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration |
Contractual warranty | |
Warranty | 1 year on-site repair or replace |
Reviews
There are no reviews yet.